Custom Manufactured HEMP/EMP Filters

HEMP/EMP Filters
[click to enlarge]
HEMP Filters Power Line
 

Capability:
Captor Corporation
, the expert in electromagnetic interference filters, offers custom HEMP/EMP filters, that target power, signal and tempest interference. We perform the design, engineering, layout, manufacturing and assembly as well as the testing, verification, consulting, prototyping and research and development. We provide assembly of components, connectors, and termination configurations while offering options such as HEMP protection modules, certified PCI data and custom tailoring.

Captor can provide existing designs for power lines, audio-data lines and control-signal lines for AC/DC power, telephone, analog fire alarms, servo motors and synchro transmitters. Ratings are 0 to 480 volts and 0 to 100 amps although higher currents are possible. Utilizing non-nutritive materials, our HEMP/EMP filters can be stored from -55 to +105 °C and are operational from -40 to +71 °C, up to 15,000 feet above sea level and in humidity ranging from 10 to 90%.

Captor can handle quick-turn prototypes up to large-scale production runs with lead times of two to three weeks on stock orders and 10 to 12 weeks for custom orders. For more information on our custom manufactured HEMP/EMP filters please see the chart below or contact us directly.

Standard HEMP FiltersRequest for Quote

Portfolios

Custom HEMP/EMP Filter Capabilities

General Capabilities Custom
Build to Print
Process Design
Engineering
Layout
Manufacturing
Assembly
Testing
Verification
Consulting
Prototyping
Research and Development
Equipment Automated
Manual
Components Inductors
Capacitors
Resistors
Relays
Diodes
Chokes
Varistors
Connectors Military
Commercial
Termination Configurations Quick Disconnect Terminal Tabs
Threaded Studs
Connectors
Solder Terminals
Custom
Options HEMP Protection Modules
Certified PCI Data
Custom Tailoring
Existing Designs Power Lines (Intrasite)
Audio/Data Lines (Intersite)
Control/Signal Lines (Intersite)
Existing Applications AC/DC Power
Telephone Lines
Analog Fire Alarms
Servo Motors
Synchro Transmitter
Protection Circuit
HEMP/EMP
Transient Voltage
Voltage Rating 0 to 480 V
Current 0 to 100 Amps
Higher Currents Possible
Insertion Loss 100 dB minimum from 14 kHz to 10 GHz
Frequency DC to 400 Hz
Operating Temperature -40 to +71 °C
Storage Temperature -55 to +105 °C
Altitude Maximum 15,000 feet above sea level
Humidity 10 to 90 %
Fungus Non-nutritive materials are used
Enclosures (Corrosion) Hermetically Sealed Steel
Aluminum
Plating Tin-Lead
Standards MIL-STD-188-125-1
Input Inductive
Inspection 100% Test
Visual
AQL
Testing Altitude
Temperature Cycling
Shock
Vibration
Electrical
Mechanical
Environmental
Quality Control Test Plan
Test Report
Secondary Operations (In-House) Assembly
Machining
Forming
Bending
Welding
Quick Turn Prototypes
Production Volume Prototype to Large Scale Production Runs
Typical Lead Times 1 week (Stock)
10 to 12 weeks (Custom)
1 to 3 weeks (Prototype)

Additional Information

Industry Focus Electrical
Electronic
Military
Aerospace
Commercial
Industry Standards AS9100 Rev C
ISO 9001:2008
IPC 610